Product datasheet - KVKVEB-6/30
Residual current circuit breaker, electr., 2P, 1 mod, B kar.
B6, 30mA, 6kA, AC, E3
Item number:KVKVEB-6/30
(EAN: 5997374176873)
B6, 30mA, 6kA, AC, E3
Residual current circuit breaker, electr., 2P, 1 mod, B kar.
Item number:KVKVEB-6/30 (EAN: 5997374176873)Technical data B6, 30mA, 6kA, AC, E3
More than 100 pc(s) in stock
Net
33.60526 EUR
33.60526 EUR
Gross
42.67868 EUR
Number of poles (total):
2
Number of protected poles:
1
Rated voltage:
230 V
Rated insulation voltage Ui:
690 V
Rated impulse withstand voltage Uimp:
4 kV
Rated current:
6 A
Rated fault current:
0.03 A
Leakage current type:
AC
Current limiting class:
3
Voltage type:
AC
Frequency:
50/60 Hz
Release characteristic:
B
Concurrently switching neutral conductor:
Yes
Ambient temperature during operating:
-25 -55 °C
Width in number of modular spacings:
1
Flush-mounted installation:
Yes
Degree of protection (IP):
IP20
Connectable conductor cross section solid-core:
1 -16 mm²
Connectable conductor cross section multi-wired:
1 -16 mm²
Warranty:
2 year
KVKVEB-6/30 | 6 | 30 |
The combined protective switch is mainly used in electrical installations of buildings, for personal, overload and short circuit protection. It is especially suitable for electrical protection of rooms with increased safety requirements. The current transformer of the protective switch, namely the magnetic quick breaker and the bimetallic, thermal, residual current breaker are placed in the same box. It breaks the circuit of the protected device only in one pole. The device is equipped with optical display for signaling the operational state: the red color marks the “ON” state of the switch. Correct operation of the device can be controlled by pushing the “T” test button. The test should possibly be effected monthly.
Rated operating voltage:
|
220 – 240 V AC
|
Rated insulation voltage:
|
690 V AC
|
Rated impulse withstand voltage:
|
6 kV
|
Applicable shunt fuse:
|
max. 40 A gG
|
Short circuit withstand (with shunt fuse):
|
25 kA
|
Rated switching ability:
|
max. 300 A (cos = 0,65)
|
Rated short circuit breaking ability:
|
6 kA
|
Electrical life:
|
4000 switching cycles
|
Mechanical life:
|
20 000 switching cycles
|
Protection against external effects:
|
Shock and UV proof plastic housin
|
The thermal trip units are inaccessible from outside
|
|
Number of poles:
|
1
|
Protection degree:
|
IP 40
|
Mounting:
|
Clip-on 35×7,5 mm size mounting rail
|
Way of termination:
|
With female clips
|
Terminal capacity:
|
1,0 –16 mm2
|
Locking:
|
The switching arm is lead-sealable in „OFF” position
|
Ambient temperature:
|
-25…+50 °C
|
Tracon code
|
Tripping characteristics |
Rated current
|
Rated residual current |
KVKVEB-6/30
|
„B”
|
6 A
|
30 mA
|
Related products