Product datasheet - TR1F1810E7
Contactor
660V, 50Hz, 18A, 7,5kW, 48V AC, 3×NO+1×NO
Item number:TR1F1810E7
(EAN: 5997374142519)
660V, 50Hz, 18A, 7,5kW, 48V AC, 3×NO+1×NO
Contactor
Item number:TR1F1810E7 (EAN: 5997374142519)Technical data 660V, 50Hz, 18A, 7,5kW, 48V AC, 3×NO+1×NO
More than 1 pc(s) in stock
Net
25.18421 EUR
25.18421 EUR
Gross
31.98395 EUR
Rated control supply voltage Us at AC 50HZ:
45.6 -50.4 V
Voltage type for actuating:
AC
Rated operation current Ie at AC-1, 400 V:
32 A
Rated operation current Ie at AC-3, 400 V:
18 A
Rated operation power at AC-3, 400 V:
7.5 kW
Rated operation current Ie at AC-4, 400 V:
7.7 A
Rated operation power at AC-4, 400 V:
3 kW
Type of electrical connection of main circuit:
Screw connection
Number of normally open contacts as main contact:
3
Warranty:
2 year
The TR1D and TR1F type contactors are applicable for remote controlled on/off switching of low voltage electric units in 9-95 A current range. The two types are different only by outlook; their technical parameters are the same.
General technical data
Operating voltage range:
|
0,85-1,1 U
n
|
Ambient temperature:
|
-25 °C ... +50 °C
|
Mounting position:
|
vertical, deviation max. ±30°
|
Art of mounting:
|
on mounting plate or clip on 35×7,5 mm mounting rail
|
Operating
voltage
Un
|
Contacts
|
Marking of Of
terminals
|
Tracon code
|
18A/AC-3
|
|||
48 V~
|
3 main + auxiliary 1 closed (NO) |
|
TR1F1810E7
|
Rated insulating voltage U
i (V)
|
660 V
|
|
Rated operating voltage U
e (V)
|
660 V, 50 Hz
|
|
Rated operating current
Ie (A)
|
AC-1
|
32
|
AC-3
|
18
|
|
AC4
|
7,7
|
|
Max. switchable
motor power P
e (kW)
|
220/230 V AC-3
|
4 |
380/400 V AC-3 | 7,5 | |
380/400 V AC-4 | 3 | |
415 V AC-3
|
9 | |
500 V, 660/690 V AC-3
|
10 | |
Short circuit
protection device
|
rated current (A)
|
20
|
tripping characteristics
|
aM
|
|
Max. switching frequency (switch/hour, AC-3)
|
3600
|
|
Mechanical life (
kj)
|
3x10
6
|
|
Electrical life (
kj)
|
1x10
6
|
|
Terminal capacity (mm
2)
|
6
|
|
Protection degree of main / coil contacts
|
IP 20
|
|
Power consumption – pick-up / hold (VA)
|
60/7
|
|
Terminal capacity of coil terminal (mm2) | 1..4 |
Dimensions
Fixed on mounting plate | Fixed on mounting rail | ||||||||||||||||
|
|