Product datasheet - MZSVK3-12
Middle voltage heat shrink termination kit, outdoor
1×95-150mm2, 12kV
Item number:MZSVK3-12
(EAN: 5997374115780)
1×95-150mm2, 12kV
Middle voltage heat shrink termination kit, outdoor
Item number:MZSVK3-12 (EAN: 5997374115780)Technical data 1×95-150mm2, 12kV
1 pc(s) in stock
Extra discount: 5,00 %
Net
100.46053 EUR 95.43750 EUR
100.46053 EUR 95.43750 EUR
Gross
127.58487 EUR
121.20563 EUR
Type:
Other
Suitable for:
Other
Warranty:
2 year
Heat shrinkable, outdoor termination kits for single-core, XLPE insulated, wire or tape screened cables (e.g. N2XSY, 2XSY, NA2XSY, A2XSY, NA2XS2Y, A2XS2Y types) with aluminum or copper conductor, without connectors.
The kit contains one, single-core termination.
Tracon code
|
Size
(mm2)
|
Max. voltage (kV) |
Cable cross-section (mm2) |
Length of
termination (mm)
|
Number of rain
shields
|
MZSVK3-12
|
1×95-150
|
12
|
95-150
|
350
|
2
|
|
|||||
Sealing of the (C) and (D) layers of the medium voltage cable (B) is made by using stress control tape (2) and stress control tube (3). Possible gaps on the cable lug (1) are eliminated by using filling mastics (4).
Cable screening (E) elements: In case of wire screening: PVC tape (7), shielded earth connection lug (11). In case of tape screening: adhesive copper tape (8), tinned copper mesh (9), constant force spring (10). The termination is protected against weathering, UV radiation and mechanical effects by antitrack tube (5) and rain sheds (6), shrunk onto the outer jacket (F). |
The proper copper or aluminum lugs (1) (no part of the kit) should be selected based upon the cross section of the cable core (A).